山邦蓄电池SPT12-9 12V9AH 免维护铅酸蓄电池UPS数据中心专用
规格 Specifications
额定电压Rated Voltage 12V
尺寸Dimension
标称容量 Nominal Capacity(C2o,1.75V/cell) 9.0Ah
长 Length 151±2mm(5.94 inches)
宽Width 65±1mm(2.56inches
高 Container Height93.5±1mm (3.68 inches)总高(含端子)Total Height99.5±1mm (3.92 inches)
重量Approx Weight 2.17kg(4.78 lbs)
端子Terminal T1/T2
外壳材料Container Material ABS
7.00Ah C20(0.350A,1.75V/cell)
6.62Ah C10(0.662A,1.75V/ceIl)
额定容量Rated Capacity(25°C)6.00Ah C5(1.20A,1.75V/cell)
5.37Ah C3(1.79A,1.75V/celI)
4.60Ah C1(4.60A,1.60V/ceII)
5S放电电流Max.Discharge Current 105A(5s)
内阻Internal Resistance(25°C) Approx 25mΩ
放电Discharge -20~55℃(-4~131°F)
运行温度OperatingTemp.Range充电Charge -20~40°C(-4~104°F)
存储Storage -15~50℃(5~122F)
推荐温度Nominal Operating Temp.Range 25±5°C(77±5°F)
充电电流Max.Charging Current(25°C) 2.10A
充电电压温度补偿Charge voltageTemp.Coefficient
充电电压 Charge voltage(25°C)均充 Equalization2.35~2.40V/cell-4mV/单格/°C浮充Float2.25~2.30V/cell-3mV/单格/°C
循环Cycle2.40~2.50V/cell-5mV/单格/°C
40℃(104F) 103%
温度对容量影响Effect of temp.to Capacity25℃ (77°F) ***
0°℃ (32F) 86%
山邦蓄电池SPT12-9 12V9AH 免维护铅酸蓄电池UPS数据中心专用
负载保护。
a)UPS负载为额定容量的110%~130%;若UPS从旁路跳转至逆变前,检测到负载超过110%,则无法进入逆变状态,此时UPS每0.5s鸣叫一次,并于面板显示状态。若开机后,检测到负载在110%~130%之间,则UPS每0.5s鸣叫一次,并于面板显示状态,10s后UPS跳至旁路模式;此后若负载减轻至***以下,则UPS重新软开机。若UPS在蓄电池供电模式下检测到负载在110%~130%之间,则UPS每0.5s鸣叫一次,并于面板显示状态;若负载未减轻至***以下,则10s后UPS转至旁路模式,此状态只有按OFF键才能解除。UPS负载为额定容量130%以上:若开机后检测到负载大于130%,则UPS每0.5s鸣叫一次,并于面板显示状态,同时UPS转至旁路状态。此后若负载减轻至***以下,则UPS重新开机。若UPS在蓄电池供电模式下检测到负载大于130%,则UPS每0.5s鸣叫一次,并于面板显示状态;同时UPS转至旁路模式,此状态只有按OFF键才能解除。
山邦蓄电池SPT12-9 12V9AH 免维护铅酸蓄电池UPS数据中心专用
故障诊断处理
故障现象1:无充电电压或充电电压异常。
故障分析检修:山特C3kVA UPS 的充电器电路,针对无充电电压或充电电压异常的故障现象,用万用表的二极管挡分别测试BR01、U202、U203、VM208其值为“0”时,为该器件故障,应予以更换。若故障仍未消除,用万用表的电阻挡分别测试图7-8中的R238、U206(6-5)、TX1、R230,R238正常值为100k;故障时为无穷大。U206(6-5)正常值为47k2;故障时为无穷大。TX1的阻值若为无穷大可判断TX1故障。R230正常值为0.5;故障时为无穷大。在故障元器件更换后,可能出现充电电压高于或低于正常值现象,可通过调节VR301,使之符合标准,即认为充电电路正常。