保护电路
IEC 类别 | C1 |
---|---|
C2 | |
C3 | |
D1 | |
额定电压 UN | 24 V DC |
持续工作电压UC | 30 V DC |
21 V AC | |
额定电流 | 600 mA (56 °C) |
UC时,有效工作电流IC | ≤ 5 µA |
残流IPE | ≤ 1 µA |
标称放电电流In (8/20) µs(线芯-线芯) | 5 kA |
标称放电电流In (8/20) µs(线芯-地) | 5 kA |
标称放电电流In (8/20) µs(线芯-信号接地) | 5 kA |
脉冲放电电流Iimp (10/350) µs(线芯-线芯) | 0.5 kA |
脉冲放电电流Iimp (10/350) µs(线芯-地) | 0.5 kA |
脉冲放电电流Iimp(10/350) µs(线-信号地) | 0.5 kA |
总放电电流Itotal (8/20) µs | 10 kA |
电压保护水平Up(线芯-线芯) | ≤ 150 V (C1 - 1 kV/500 A) |
≤ 275 V (C2 - 10 kV / 5 kA) | |
≤ 45 V (C3 - 25 A) | |
≤ 55 V (C3 - 100 A) | |
电压保护水平Up(线芯-地) | ≤ 750 V (C1 - 1 kV/500 A) |
≤ 750 V (C2 - 10 kV / 5 kA) | |
≤ 1.1 kV (C3 - 25 A) | |
≤ 1.2 kV (C3 - 100 A) | |
电压保护水平Up(线-信号地) | ≤ 80 V (C1 - 1 kV/500 A) |
≤ 125 V (C2 - 10 kV / 5 kA) | |
≤ 45 V (C3 - 25 A) | |
≤ 55 V (C3 - 100 A) | |
电压防护等级Up静态(线芯-线芯) | ≤ 75 V (C1 - 1 kV/500 A) |
≤ 120 V (C2 - 10 kV / 5 kA) | |
电压防护等级Up静态(线芯-接地) | ≤ 75 V (C1 - 1 kV/500 A) |
≤ 120 V (C2 - 10 kV / 5 kA) | |
电压保护水平Up静态(线-信号地) | ≤ 750 V (C1 - 1 kV/500 A) |
≤ 750 V (C2 - 10 kV / 5 kA) | |
响应时间tA(线芯-线芯) | ≤ 1 ns |
响应时间tA(线-信号地) | ≤ 1 ns |
响应时间tA(线芯-地) | ≤ 100 ns |
输入衰减aE,对称 | 典型值 0.3 dB (≤ 8.7 MHz / 150 Ω) |
输入衰减aE,非对称 | 典型值 0.3 dB (≤ 10.5 MHz / 150 Ω) |
截止频率fg(3dB),150 Ω 对称系统 | 典型值 60 MHz |
截止频率fg(3dB),非对称。 (地)在150 Ω 系统中 | 典型值 60 MHz |
电容(线芯-线芯) | 典型值 32 pF |
容量(线-信号地) | 典型值 32 pF |
每条路径的电阻 | 1.65 Ω ±20 % |
需要的备用保险丝 | 630 mA (FF) |
电涌电流电阻(导线-导线) | C1 - 1 kV / 500 A |
C2 - 10 kV / 5 kA | |
C3 - 100 A | |
电涌电流电阻(导线-接地) | C1 - 1 kV / 500 A |
C2 - 10 kV / 5 kA | |
C3 - 100 A | |
D1 - 500 A | |
电涌电流承载能力(线-信号地) | C1 - 1 kV / 500 A |
C2 - 10 kV / 5 kA | |
C3 - 100 A | |
D1 - 500 A | |
脉冲复位时间(导线-导线) | ≤ 600 ms |
脉冲复位时间(导线-接地) | ≤ 30 ms |
脉冲复位时间(线-信号地) | ≤ 600 ms |
返回顶部
附加技术数据
总放电电流I total max (8/20) µs | 20 kA (1x) |
---|