IC200PWR012
IC200PWR012
组态软件使创建自定义配置成为可能
VersaMax PLC系统。对于CPUE05,也用于配置Ethernet Global Data。
当您进入硬件配置为VersaMax设备文件夹,默认视图
是机架(主)。新的配置已经包含一个默认电源(PWR001)。
CPU (CPU001)。两者都可以很容易地改变,以匹配PLC中的实际硬件
系统。
I/O Scan-Stop Determines whether I/O is to be scanned
while the PLC is in STOP mode.
No Yes, No
Powerup Mode Selects powerup mode. Last Last, Stop, Run
Logic/Configuration
From
Source of program and configuration when
the PLC is powered up.
RAM RAM, Flash
Registers Selects source of register data when PLC is
powered up.
RAM RAM, Flash
Passwords Determines whether the password feature is
enabled or disabled. (If passwords are
disabled, the only way to enable them is to
clear the PLC memory.)
Enabled Enabled,
Disabled
Checksum Words per
Sweep
The number words in the application
program to be checksummed each sweep
8 8 to 32
Default Modem
Turnaround Time
Modem turnaround time (10ms/unit) This is
the time required for the modem to start
data transmission after receiving the
transmit request.
0mS 0–255mS
Default Idle
Time
Time (in seconds) the CPU waits to receive
the next message from the programming
device before it assumes that the
programming device has failed and
proceeds to its base state. Communication
with the programmer is terminated and will
have to be reestablished.
10 1–60
SFC Timer
Faults
Enables or disables viewing of SFC Timer
faults.
Disabled Enabled
/Dis abled
SNP ID None Editable
Switch
Run/Stop
Determines whether the switch will control
Run/Stop mode operation
Enabled Enabled,
Disabled
Switch Memory
Protect
Determines whether the switch will control
RAM memory protection.
Disabled Enabled,
Disabled
Diagnostics Unless your application requires unusually
fast power up, leave this setting ENABLED.
The DISABLED setting causes the PLC to
power up without running diagnostics.
Enabled Enabled,
Disabled
Fatal Fault
Override
Determines whether fatal faults will
normally be overridden.
Disabled Enabled,
Disabled
要配置PLC,您需要:
•配置机架类型(非扩展、单端扩展或多机架)
扩大)。
•配置电源类型和任何升压电源和载体。(注意
CPU005和CPUE05都需要扩展3.3V电源。)
•配置CPU。这包括在必要时更改CPU类型,并分配其
参数说明请参见本章。
•配置CPU串口参数,请参考本章。
•对于CPUE05,配置其以太网参数,请参见第六章以太网
配置。
•如果系统中有扩展机架,请配置扩展模块。
•添加模块载体和定义布线分配。
•将模块放置在载体上,并选择其参数。可配置的I/O参数
各模块的说明请参见《VersaMax模块》、《电源》和《运营商用户手册》
手动(gfk - 1504)。
•保存配置文件,以便保存到PLC。
在VersaPro中提供了使用配置软件的分步说明
软件用户手册(GFK-1670)。在线帮助中提供了更多信息。