IC200PWR012设备文件夹

参数
  • 模块产品特性
  • 是否进口
  • 美国产地
福建 厦门 3天内发货 10个
厦门纵力信机械设备有限公司 2年
进入店铺 在线咨询
产品详情

IC200PWR012

IC200PWR012

组态软件使创建自定义配置成为可能

VersaMax PLC系统。对于CPUE05,也用于配置Ethernet Global Data。

当您进入硬件配置为VersaMax设备文件夹,默认视图

是机架(主)。新的配置已经包含一个默认电源(PWR001)。

CPU (CPU001)。两者都可以很容易地改变,以匹配PLC中的实际硬件

系统。


I/O Scan-Stop Determines whether I/O is to be scanned

while the PLC is in STOP mode.

No Yes, No

Powerup Mode Selects powerup mode. Last Last, Stop, Run

Logic/Configuration

From

Source of program and configuration when

the PLC is powered up.

RAM RAM, Flash

Registers Selects source of register data when PLC is

powered up.

RAM RAM, Flash

Passwords Determines whether the password feature is

enabled or disabled. (If passwords are

disabled, the only way to enable them is to

clear the PLC memory.)

Enabled Enabled,

Disabled

Checksum Words per

Sweep

The number words in the application

program to be checksummed each sweep

8 8 to 32

Default Modem

Turnaround Time

Modem turnaround time (10ms/unit) This is

the time required for the modem to start

data transmission after receiving the

transmit request.

0mS 0–255mS

Default Idle

Time

Time (in seconds) the CPU waits to receive

the next message from the programming

device before it assumes that the

programming device has failed and

proceeds to its base state. Communication

with the programmer is terminated and will

have to be reestablished.

10 1–60

SFC Timer

Faults

Enables or disables viewing of SFC Timer

faults.

Disabled Enabled

/Dis abled

SNP ID None Editable

Switch

Run/Stop

Determines whether the switch will control

Run/Stop mode operation

Enabled Enabled,

Disabled

Switch Memory

Protect

Determines whether the switch will control

RAM memory protection.

Disabled Enabled,

Disabled

Diagnostics Unless your application requires unusually

fast power up, leave this setting ENABLED.

The DISABLED setting causes the PLC to

power up without running diagnostics.

Enabled Enabled,

Disabled

Fatal Fault

Override

Determines whether fatal faults will

normally be overridden.

Disabled Enabled,

Disabled

要配置PLC,您需要:

•配置机架类型(非扩展、单端扩展或多机架)

扩大)。

•配置电源类型和任何升压电源和载体。(注意

CPU005和CPUE05都需要扩展3.3V电源。)

•配置CPU。这包括在必要时更改CPU类型,并分配其

参数说明请参见本章。

•配置CPU串口参数,请参考本章。

•对于CPUE05,配置其以太网参数,请参见第六章以太网

配置。

•如果系统中有扩展机架,请配置扩展模块。

•添加模块载体和定义布线分配。

•将模块放置在载体上,并选择其参数。可配置的I/O参数

各模块的说明请参见《VersaMax模块》、《电源》和《运营商用户手册》

手动(gfk - 1504)。

•保存配置文件,以便保存到PLC。

在VersaPro中提供了使用配置软件的分步说明

软件用户手册(GFK-1670)。在线帮助中提供了更多信息。