取消

ADV141-P53 [CE标志](*1)(横河)-Yokogawa

参数
  • 标准规格产品特性
  • 是否进口
  • 日本产地
福建 厦门 3天内发货 10个
厦门纵力信机械设备有限公司 1年
进入店铺 在线咨询
产品详情

ADV141-P53

光ESB总线中继器模块单元

电源模块、光ESB总线中继器模块安装在一个单元中。

详细信息请参见“光总线中继器模块单元(适用于AFV30/AFV40)”(GS 33K50F50-50E)。

F03E.ai

ANT10U

Io1 io2 io3 io4

l I/O模块






I/O模块包括模拟I/O模块、数字I/O模块和通信模块。有几个

模拟I/O模块的类型,包括隔离通道型、隔离型和非隔离型。

此外,为了能够从CENTUM V, CENTUM-XL和µXL兼容模块中进行替换,因此提供

信号调节器的系统线可以连接到这些兼容的模块上。

对于I/O模块,可选择防环境支持(温度环境支持、G3支持)

***。

I/O模块是防爆产品。详见《防爆》(TI 33Q01J30-01E)。

模拟I/O模块

AAI141

模拟输入模块

(4至20 mA, 16通道,

Non-Isolated)

X X X X X X X

AAV141

模拟输入模块

(1至5v, 16通道,

Non-Isolated)

X X X X X X X

AAV142

模拟输入模块

(-10至10V, 16通道,

Non-Isolated)

X X X X X X X

AAB141

模拟输入模块

(1至5 V/4至20 mA, 16通道,

Non-Isolated)

X X X X X X X

AAI841

模拟I/O模块

(4 ~ 20ma输入,4 ~ 20ma

输出,

8路输入/ 8路

输出,Non-Isolated)

X X X X X X X

AAB841

模拟I/O模块

(1 ~ 5v输入,4 ~ 20ma

输出,

8路输入/ 8路

输出,Non-Isolated)

X X X X X X X

AAB842

模拟I/O模块

(1至5v /4至20ma输入,4至20

mA输出,8通道输入/8-

通道输出(非隔离)

X X X X X X X

AAV542

模拟输出模块

(-10至10V, 16通道,

Non-Isolated)

X X X X X X X

AAI143

模拟输入模块

(4至20 mA, 16通道,

孤立的)

X X X X X X X X

AAI543

模拟输出模块

(4至20 mA, 16通道,

孤立的)

X X - X X (*1) X X X -

AAV144

模拟输入模块

(-10至10V, 16通道,

孤立的)

X X X X X X X X

AAV544

模拟输出模块

(-10至10V, 16通道,

孤立的)

X X X X X X X X

AAT141

TC/mV输入模块

(c) r, j, k, e, t, b, s, n /

mV: -100至150 mV, 16通道,

孤立的)

X X X X X X X

AAR181

RTD输入模块

(RTD: Pt100 Ω, 12通道,

孤立的)

X X X X X X X

AAI135

模拟输入模块

(4至20 mA, 8通道,隔离

通道)

X X X X X X X X

AAI835

模拟I/O模块

(4至20 mA, 4通道输入/

4通道输出,隔离

通道)

X X X X X X X X

AAT145

TC/mV输入模块

(TC: R、J、K、E、T、B、S、N/mV)

-100至150 mV, 16通道,

孤立的通道)

X X X X X X X X

X:可用。-:不可用。

注:所有I/O模块均符合CSA, EAC Marking和CE Marking安全标准,CE Marking, EAC

标识,和RCM EMC的符合性标准。除了内置屏障的I/O模块外,其他I/O模块都符合KC

标记EMC符合性标准。

*1: AAI543-6,-F(快速响应),仅支持G3

Analog I/O Modules

AAR145

RTD/POT Input Module

(RTD: Pt100 Ω/POT: 0 to 10 kΩ,

16-Channel, Isolated Channels)

X X – X X X X X – –

AAP135

Pulse Input Module

(8-Channel, Pulse Count, 0 to

10 kHz, Isolated Channels)

X X – X X X X X – –

AAP149

Pulse Input Module for

compatible PM1

(16-Channel, Pulse Count, 0 to

6 kHz, Non-Isolated)

X X – – X

(G3 only) – – – – –

AAP849

Pulse Input/Analog Output

Module for compatible PAC

(Pulse Count, 4 to 20 mA,

8-Channel Input/

8-Channel Output,

Non-Isolated)

X X – X X

(G3 only) – – – – –

– Digital I/O Modules

ADV151 Digital Input Module

(32-Channel, 24 V DC, Isolated) X X (*2) – X X X X X – –

ADV551 Digital Output Module

(32-Channel, 24 V DC, Isolated) X X – X X X X X – –

ADV141

Digital Input Module

(16-Channel, 100 V AC,

Isolated)

X X – X X X – – – –

ADV142

Digital Input Module

(16-Channel, 220 V AC,

Isolated)

X X – X X – – – – –

ADV157

Digital Input Module

(32-Channel, 24 V DC,

Pressure Clamp Terminal

Support Only, Isolated)

X X – – X

(G3 only) X – X – –

ADV557

Digital Output Module

(32-Channel, 24 V DC,

Pressure Clamp Terminal

Support Only, Isolated)

X X – – X

(G3 only) X – X – –

ADV161 Digital Input Module

(64-Channel, 24 V DC, Isolated) X X – X X

(G3 only) X X X – –

ADV561 Digital Output Module

(64-Channel, 24 V DC, Isolated) X X – X X

(G3 only) X X X – –

ADR541

Relay Output Module

(16-Channel, 24 to 110 V

DC/100 to 240 V AC, Isolated)

X X – X X X – – – –

– Digital I/O Modules (ST Compatible)

ADV859

Digital I/O Module for

Compatible ST2

(16-Channel Input/16-Channel

Output, Isolated Channels)

X X – X (*3) X

(G3 only) – – – – –

ADV159

Digital Input Module for

Compatible ST3

(32-Channel Input, Isolated

Channels)

X X – X (*3) X

(G3 only) – – – – –

ADV559

Digital Output Module for

Compatible ST4

(32-Channel Output, Isolated

Channels)

X X – X (*3) X

(G3 only) – – – – –

X: Available. –: Not available.

Note: All the I/O modules are compliant with the CSA, EAC Marking, and CE Marking safety standards, CE Marking, EAC

Marking, and RCM EMC conformity standards. I/O modules, except the ones with built-in barrier, are compliant with KC

Marking EMC conformity standard.

*2: Only ADV151-P is allowed to be installed in the ER Bus Node Unit. ADV151-E is not allowed to be installed in the ER Bus

Node Unit.

*3: Dual-redundant configuration is possible only when the ST card duplexed with the existing CENTUM-XL is replaced.


为您推荐
供应商网> 工控系统及装备> 其他工控系统及装备> ADV141-P53 [CE标志](*1)(横河)-Yokogawa
    在线问
    产品参数
    1/5
    面议 在线咨询
    进店 客服 获取最低报价 拨打电话
    ADV141-P53 [CE标志](*1)(横河)-Yokogawa
    ¥面议
    • 采购产品
    • 采购数量
    • 联系电话
    获取报价 获取报价