Himod M系列是HIROSS公司2005年推出全新HIMOD M系列,秉承HIROSS系列模块化机房专用空调的全部优点,高精度恒温控制型弥漫式送风。
M series is launched in 2005. It has all of the advantages of our HIROSS series modular room air-conditioning, high precision temperature control type, and diffuse type air flow.
弥漫式送风型号为S/MX XKA
Diffuse air flow model – S/MX XKA
弥漫式送风空气在机房的循环方式
Diffuse type air circulation in the computer room
弥漫式送风空气在机房的循环方式
Diffuse type air circulation in the computer room
冷空气由空调下部送出,在地板平面流动,依据流体力学原理,冷空气分布在机柜的中部和下部,在机柜的周围形成冷空气的“包围”,空气受热上升,在房间内依靠“热动力”流动。计算机机柜在底部吸入冷空气,计算机或机柜本身的强制通风设备完成空气的循环,受热的空气由机柜上部排出。
Cold air from air conditioning is out in the floor plane flow. Based on the principle of fluid mechanics, the cold air is distributed in the middle and lower cabinet. The cabinet is formed around the "siege" of cold air, and the hot air rises relying on the "thermal" flow in the room. Computer cabinet at the bottom is sucked the cold air, forced ventilation device of a computer or the cabinet itself complete air circulation, the heated air is discharged by the top of cabinet.
弥漫式送风空气在机房内的循环方式
相对于下送风方式,弥漫式送风方式不需要架空地板,而单位面积的热负荷可提高10%,同时房间层高要求降低,普通房间都可作为机房使用。
由于机柜被冷空气包围,相对于下送风方式,弥漫式送风方式下机柜的冷却效果更佳。
而对于上送风方式,弥漫式送风方式不需要风管,避免了房间的温度的不均匀的情况的发生 ,同时可以节能10%-20%,降低空调制冷量需求10%。
Diffuse type air circulation in the computer room
Relative to the lower air supply, the diffuse type does not require overhead floor, while the heat load per unit area can be increased by 10%, and reduces the requirement of storey rooms, common room can be room.
The cabinet is surrounded by the cold air relative to the lower air supply, and it provides better cooling effect for the diffuse type.
But for the upper air supply, the diffuse type ventilation does not need wind pipe to avoid the inhomogeneous temperature of the room, and also can save energy up to 10%-20% and reduce air conditioning demand of 10%.
弥漫式送风方式的优势
单位面积热负荷提高10%,降低机房建筑层高要求,节省安装费用,节省运行费用多种冷却方式,包括风冷,水冷,乙二醇冷却,乙二醇自然冷却,冷冻水,双冷源等,配合用户室外的综合现场条件对冷却的要求,储液罐式冷凝器,可***机组在环境温度低至-34.4℃都可正常运行,运用了大量环保节能技术,包括采用无环境污染的原材料和机组防腐涂料,大量采用可重复使用的部件,增强机组的可维护性,***的微处理器具有顺序优先启动功能,使机组部件磨损平均,延长机组使用寿命,双制冷系统运行,节能且更加可靠,高效低能耗的压缩机 ,采用“模糊逻辑控制”和“温度控制”等***调控技术,提高控制精度,降低能耗,延长机组使用寿命 ,***的故障自动报警系统和开机自诊断功能,使诊断处理机组的问题更加快捷。
The advantage of diffuse type
The heat load per unit area was increased by 10%. The diffuse type reduces the height of building, saves the installation cost, and saves multiple cooling mode and operating costs including air cooling, water cooling, ethylene glycol, ethylene glycol natural cooling, freezing water, double cold source. Cooperate with the general conditions of outside for the requirement of cooling, the liquid storage tank condenser can guarantee the normal operation of the unit achieving the low temperature to -34.4℃. The use of a large number of environmental protection and energy saving technologies includes the use of raw materials and the anticorrosive paint without environmental pollution, extensive use of reusable components, and enhanced unit maintainability. The advanced microprocessor has the priority of starting function, makes the unit parts wear on average, and prolongs the service life. Dual fluid refrigeration system increases the energy saving and is more reliable, high efficiency and low energy consumption. The compressor is used the "advanced control using fuzzy logic control" and "absolute temperature control" technology to improve the control precision, reducing energy consumption, prolonging the service life, automatic fault alarm system, and booting diagnosis function which makes the diagnostic problems more quickly.
应用的范围 Application
* 电信交换机房 * 网管中心
* Communication room * Network center
* 卫星控制中心 * IDC数据中心
* Satellite control center * IDC data center
* 动力机房 * 实验室
*Power room * Laboratory
* 培训中心 * 标准室
*Training center * Standard room
* 洁净室 * 工业控制中心
* Clean room * Industry control center
* 精密加工中心 * UPS机房和电池室
* Precision machine center * UPS room and battery room
Direct expansion air cooling/water cooling - AW (直接膨胀风冷、水冷型 – A/W):
Air flow: below, above (送风方式:下送风、上送风)
Model (型号)M25M29M31M34M35M41
Characteristics (性能)
Total cooling cap. (总冷量)kW26.529.731.336.237.042.8
Humidity cap. (湿冷量)kW24.227.230.334.135.143.4
Hum. Heat ratio (湿热比)0.910.920.970.940.950.95
EER (效能比)3.583.353.513.623.583.52
Compressor Q. (压缩机数量)n111211
Compressor power (压缩机功率)kW5.896.966.942x3.827.9610.0
Fan Q.(风机数量)n112222
Fan input power (风机输入功率)kW1.521.901.992.382.382x1.51
Wind rate (风量)m³/h7100788010040111401122012470
Max. Pressure (风压-上/下风送)Pa380280420350340380
Noise (噪音-下送风)db(A)535558616158
Humidity (加湿量)Kg/h9913131313
Power of hum.(加湿功率)kW5.85.89999
Heating power (加热功率)kW7.57.515151515
Tube 气/液管径Mm22/1822/1822/1816/1628/2228/22
标凖水冷型 – W (进水温度30℃,出水温度45℃) standard water-cooling type - W (inlet water temperature of 30 ℃, outlet water temperature of 45 ℃)
Water flow (水流量)l/s0.640.710.742x0.430.871.08
Pressure (水端压降)kPa191213121312
Pipe (水管管径)Inch1”1”1 1/4”2x3/4”1 1/4”1 1/4”
Max. power consumption (耗电量)kW14.916.323.021.22528
Weight (净重)kg425430575590580600
Frozen Water (冷冻水型):
Model (型号)M44M55M66M77L90UL10UL12UL14UL15U
Characteristics (性能)
Total cooling cap. (总冷量)kW43.658.668.883.590.7103.4117.9142.8158.9
Humidity cap. (湿冷量)kW34.749.756.264.876.883.997.4111.7121.5
Hum. Heat ratio (湿热比)0.800.850.820.780.850.810.830.780.76
Fan Q.(风机数量)n122222333
Wind rate (风量)m³/h86501374015370159501906020400231002510026070
Max. Pressure (风压-上/下风送)Pa170340245170330310290250250
Noise (噪音-下送风)dB(A)5558606258.76162.162.163.8
Water flow (水流量)l/s2.082.793.283.994.334.935.626.817.58
Pressure (水端压降)kPa9189658175791048080
Pipe (水管管径)inch1 1/4”1 1/4”1 1/2”1 1/2”2”2”2 1/2”2 1/2”2 1/2”
Width (宽度)mm100017501750175020502050255025502550
Length (长度)mm850850850850890890890890890
Weight (净重)kg330480550600620610740800810
Free cooling – F (自然冷却型 - F):
Air flow: below, above (送风方式:下送风、上送风)
Model (型号)M25M31M34M35M41M42M47M50M58L83U
Characteristics (性能)
Total cooling cap. (总冷量)kW25.731.534.435.744.041.151.651.757.175.8
Humidity cap. (湿冷量)kW22.729.432.132.840.238.045.644.948.568.9
Hum. Heat ratio (湿热比)0.880.930.930.920.910.920.880.870.850.91
Fan Q.(风机数量)n1221222222
Wind rate (风量)m³/h7100100401114011220124701253013550135401458019010
Max. Pressure (风压-上/下风送)Pa270320250200330330250250190200
Noise (噪音-下送风)dB(A)54595960595962606265.7
Width (宽度)mm1000175017501750175017501750175017502550
Length (长度)mm850850850850850850850850850890
Weight (净重)kg5107157257207307457407557701140
Dual fluid air cooling/water cooling – D/H (双冷源风冷、水冷型 – D/H ):
Air flow: below, above (送风方式:下送风、上送风)
Model (型号)M25M31M34M35M41M42M47M50M58L83U
Characteristics (性能)
Total cooling cap. (总冷量)kW25.731.534.435.744.041.151.651.757.181.0
Humidity cap. (湿冷量)kW22.729.432.132.840.238.047.047.551.571.1
Hum. Heat ratio (湿热比)0.880.930.930.920.910.920.910.920.900.88
EER (效能比)3.313.293.303.263.283.363.253.333.163.11
Characteristic of water cooling (水冷性能)
Total cooling cap. (总冷量)kW29.344.647.048.156.356.860.160.162.583.7
Humidity cap. (湿冷量)kW24.837.439.940.746.146.349.649.651.972.3
Hud. Heat ratio (湿冷比)0.850.840.850.850.820.830.830.830.830.86
Compressor Q. (压缩机数量)n1121121222
Fan Q.(风机数量)n1221222222
Wind rate (风量)m³/h7100100401114011220124701253013550135401458019010
Water flow (水流量)l/s0.640.742x0.430.871.082x0.511.282x0.662x0.722x0.72
Pressure (水端压降)kPa19131213121213201212
Pipe (水管管径)inch1”1 1/4”2 3/4”1 1/4”1 1/4”2x 3/4”1 1/4”2x1 1/4”2x 1 1/4”2x 1 1/4”
Max. Pressure (风压-上/下风送)Pa270320250200330330250250190200
Noise (噪音-下送风)dB(A)54595960595962606265.7
Weight (净重)kg5107157257207307457407557701115
Diffuse air flow (弥漫式送风):
Model (型号)M25M29
Characteristics (性能)
Total cooling cap. (总冷量)kW26.429.5
Humidity cap. (湿冷量)kW23.626.5
Hum. Heat ratio (湿热比)0.890.90
EER (效能比)3.563.39
Compressor Q. (压缩机数量)n11
Fan Q.(风机数量)n11
Wind rate (风量)m³/h66807470
Max. Pressure (风压-上/下风送)Pa00
Noise (噪音-下送风)dB(A)6264
Width (宽度)mm10001000
Length (长度)mm850850
Weight (净重)kg425430