IC697CHS790G

IC697CHS790G

产品:PLC CPU模块CPX935,版本8.00

IC697CPX935-CC

目的

本文档适用于CPU模块IC697CPX935。它讨论了三个主题:(1)

关于该模块的一般信息,(2)当前固件版本8.00的特性,以及

(3)以前的固件版本7.92的功能。因为有些信息不是

可在任何其他出版物中使用,建议您保存此文档以备将来使用

参考。

FM批准

从版本IC697CPX935-BA开始,该CPU带有FM批准。,修改

不涉及任何硬件更改。

MS-DOS编程软件

从版本IC697CPX935-BA开始,MS-DOS版本7.02的副本

编程软件被封装在CPU模块中。

从版本IC697CPX935-CA开始,MS-DOS的升级副本

编程软件封装在CPU模块中。

识别

硬件识别总结如下表所示


Coprocessor Modules) use IC697PCM711J or later. It is also highly recommended that

systems using BTMs (Bus Transmitter Modules) use IC697BEM713B or later. Use of

boards of an earlier revision may result in lower system performance.

PCM (to CPU) Communications Timeout

The PCM has a default backplane communications timeout value of 5 seconds. After

the PCM has sent a request to the IC697 CPU, the PCM applies this timeout while

waiting on a response back from the CPU. In most cases, the CPU will respond well

within the 5–second timeout; however, in certain instances the CPU can take longer

than 5 seconds to respond. These cases are limited to LOADs or STOREs of program

and/or configuration - especially if blocks in the program are larger than 8 KBytes. Folders

containing EXE blocks (again with *.EXE files >8 KBytes) are most likely to cause problems.

Beginning in Release 6.00, Standalone C programs larger than 8 Kbytes also cause this to

happen.

Beginning in Release 5.50 of the IC697 CPUs, the CPU is guaranteed to respond

within 8 seconds. To ensure that the PCMs do not observe backplane timeouts, a file

must be loaded (using termf) to the PCM. The file must be a binary file named

CPU.ENV. The contents of this file are as follows (all values are specified in


为您推荐