ALR111-S50
LFS1700 Control Function for Field Control Station (for AFV30/AFV40) + LFS1750 Node Expansion
Package (for 14 nodes)
No. of ALR111/ALR121/ALE111/ALP111 or ALP121/AGS813/AGP813
modules
Max. 32 units/FCS
(Max. 16 pairs for dual-redundant operation) (*1)
No. of ALF111 modules Max. 64 units/FCS
(Max. 32 pairs for dual-redundant operation)
No. of all the communication modules Max. 64 modules/FCS (*1) (*2)
I/O data capacity for communication 1000 word/ALE111
No. of communication definition 128 definitions/ALE111
No. of communication functions Max. 8 types/FCS (*1) (*3)
Communication I/O data capacity Max. 8000 words/FCS
(incl. data from other communication function)
*1: ALP111 and ALP121 cannot be mounted on the same FCS together.
*2: This is the sum of ALR111, ALR121, ALE111, ALF111, ALP111 or ALP121, AGS813, and AGP813 modules.
*3: This is the sum of communication functions of ALR111, ALR121, ALE111, and ALP111 or ALP121. Note that multiple
communication functions cannot be performed on a single ALE111 module.
LFS1500 Control Function for Field Control Station (for AFV10)
No. of ALR111/ALR121/ALE111/ALP111/AGS813/AGP813 modules Max. 8 units/FCS
(Max. 4 pairs for dual-redundant operation)
No. of ALF111 modules Max. 30 units/FCS
(Max. 15 pairs for dual-redundant operation)
No. of all the communication modules Max. 30 modules/FCS (*1)
I/O data capacity for communication 1000 word/ALE111
No. of communication definition 128 definitions/ALE111
No. of communication functions Max. 4 types/FCS (*2)
Communication I/O data capacity Max. 4000 words/FCS
(incl. data from other communication function)
*1: This is the sum of ALR111, ALR121, ALE111, ALF111, ALP111, AGS813, and AGP813 modules.
*2: This is the sum of communication functions of ALR111, ALR121, ALE111, and ALP111. Note that multiple communication
functions cannot be performed on a single ALE111 module.
LFS1500 Control Function for Field Control Station (for AFV10) + LFS1550 Node Expansion Package (for
AFV10)
No. of ALR111/ALR121/ALE111/ALP111/AGS813/AGP813 modules Max. 16 units/FCS
(Max. 8 pairs for dual-redundant operation)
No. of ALF111 modules Max. 32 units/FCS
(Max. 16 pairs for dual-redundant operation)
No. of all the communication modules Max. 48 modules/FCS (*1)
I/O data capacity for communication 1000 word/ALE111
No. of communication definition 128 definitions/ALE111
No. of communication functions Max. 4 types/FCS (*2)
Communication I/O data capacity Max. 4000 words/FCS
(incl. data from other communication function)
*1: This is the sum of ALR111, ALR121, ALE111, ALF111, ALP111, AGS813, and AGP813 modules.
*2: This is the sum of communication functions of ALR111, ALR121, ALE111, and ALP111. Note that multiple communication
functions cannot be performed on a single ALE111 module.
LFS1300 Control Function for Standard Field Control Station (for AFS30/AFS40)
No. of ALR111/ALR121/ALE111 modules Max. 6 units/FCS
(Max. 3 pairs for dual-redundant operation)
I/O data capacity for communication 1000 word/ALE111
No. of communication definition 128 definitions/ALE111
No. of communication functions Max. 4 types/FCS (*1)
Communication I/O data capacity Max. 4000 words/FCS
(incl. data from other communication function)
*1: This is the sum of communication functions of ALR111, ALR121, and ALE111. Note that multiple communication functions
cannot be performed on a single ALE111 module.
LFS1330 Control Function for Enhanced Field Control Station (for AFG30/AFG40/AFG8)
No. of ALR111/ALR121/ALE111/ALP111/AGS813/AGP813 modules Max. 16 units/FCS
(Max. 8 pairs for dual-redundant operation)
I/O data capacity for communication 1000 word/ALE111
No. of communication definition 128 definitions/ALE111
No. of communication functions Max. 4 types/FCS (*1)
Communication I/O data capacity Max. 4000 words/FCS
(incl. data from other communication function)
*1: This is the sum of communication functions of ALR111, ALR121, ALE111, and ALP111. Note that multiple communication
functions cannot be performed on a single ALE111 module.
LFS1350 Control Function for Compact Field Control Station (for AFF50)
No. of ALR111/ALR121/ALE111/ALP111/AGS813/AGP813 modules Max. 8 units/FCS
(Max. 4 pairs for dual-redundant operation)
I/O data capacity for communication 1000 word/ALE111
No. of communication definition 128 definitions/ALE111
No. of communication functions Max. 4 types/FCS (*1)
Communication I/O data capacity Max. 4000 words/FCS
(incl. data from other communication function)
*1: This is the sum of communication functions of ALR111, ALR121, ALE111, and ALP111. Note that multiple communication
functions cannot be performed on a single ALE111 module.
Installations to the ER Bus Node Unit (*1) (*2)
No. of ALR111/ALR121/ALE111/ALF111/ALP111 modules: Max. 8 units
*1: Mounting on the ER bus node unit is applicable when the FCS’s main memory is 32 Mbyte or more and EB401 firmware
revision is R3 or later.
*2: Field control units (AFV30 and AFV40) do not support ER bus node unit (ANR10).